High Current Extended Performance Range

This range of filters has been developed for use on high current three phase and neutral mains supplies. These filters employ MPE’s proprietary feedthrough filter design incorporating current compensating inductors to provide very low losses and heat dissipation, hence low running costs.

Insertion Loss Performance

Asymmetric attenuation shown as measured in 50Ω system, at all loading conditions, in accordance with CISPR-17.

Rated CurrentPart NumberDC Resistance
(mΩ)
Leakage Current*
(mA)
Length
(mm)
Width
(mm)
Height
(mm)
Approximate Weight
(kg)
800ADS26307A0.24.353300864285350
800ADS26307C0.24.353150864285350
1200ADS26314A0.14.3538001000300450
1200ADS26314C0.14.3535001000300450
1600ADS26324A0.064.3545001000350550
1600ADS26324C0.064.3541001000350550
2400ADS26334A0.044.3552001000400650
2400ADS26334C0.044.3547001000400650

Rated Voltage

  • 440/250VAC (TP&N) 50/60Hz

Alternative Voltage

  • Also suitable for 480/277VAC
  • Alternative surge arrestors may be required.

Rated Current

  • 800A to 2400A (each individual line, see table)

Current Overload

  • 1.25 x max rated current for 15 minutes.

Discharge time

  • 30 seconds to below 30V (filter incorporates discharge resistors)

Temperature Rise

  • 25°C case rise on full load

Temperature Range

  • -45°C to +85°C Storage
  • -45°C to +50°C Working

MTBF

  • >0.6 million hours (calculated using Mil Hdbk 217D)

Surge Suppression (optional)

  • 275VAC at 215J 10kA 8/20μs
  • All filters can be supplied with an integral metal-oxide varistor, fitted between each input terminal and earth. Add a suffix “V” to end of part code.

Typical Applications

  • Screened Rooms requiring low earth current leakage
  • To achieve compliance to MIL STD 461 & DEF STAN 59 411
All MPE installation filters are tested using the test methods defined within the following standards and meet or exceed the relevant performance and/or safety criteria defined within these standards:
  • Mil-F-15733
  • Mil-Std-220C
  • CISPR17:2011/BS EN 55017:2011
  • UL1283
  • LVD 2014/35/EU
  • DEF-STAN 59-411/MIL-STD-461
  • RoHS (2011/65/EU) & LVD (2014/35/EU)
  • UKCA & CE
DS XXXXX / X / X
  • Filter Part Number
  • Suffix C for standard cable entry
  • For other cable entries, see Installation Details page
  • Add suffix V for transient suppressed filter
e.g. DS26334CV

ORDERING CODE

DS XXXXX / X / X

  • Filter Part Number
  • Suffix C for standard cable entry
  • For other cable entries, see Installation Details page
  • Add suffix V for transient suppressed filter

e.g. DS26334CV