Standard Performance EMI filters for electrical connection to SP&N and TP&N mains distribution systems. The filters offer attenuation against electromagnetic noise present on the power lines between the ranges of 100kHz to 18GHz to 100dB. The supply should have a balanced return current and the case needs a solid low impedance connection to earth potential.

Insertion Loss Performance

Asymmetric attenuation shown as measured in 50Ω system, at all loading conditions, in accordance with CISPR-17.
Performance curve meets 100dB attenuation from 100kHz to 18GHz.

Standard-Performance-EMC-Filter-Range

Typical Applications

  • Screened Rooms, Server Supplies & EMC Test Chambers
  • Meets TEMPEST requirement for power filters to NATO SDIP 29/1
  • Supports compliance to MIL STD 461 & DEF STAN 59 411
Rated CurrentPart NumberDC Resistance (mΩ)Earth Leakage* (A)Length (mm)Width (mm)Height (mm)Approximate weight (kg)
16ADS23752251.80310175908
32ADS23332101.805502059516
63ADS2333461.8055020510520
100ADS2333641.8064020512022
200ADS2370822.6066047513560
400ADS260500.34.401250475150110
Rated CurrentPart Number DC Resistance (mΩ)Earth Leakage* (A)Length (mm)Width (mm)Height (mm)Approximate Weight (kg)
32ADS23333102.25504109522
63ADS2333562.755041011032
100ADS2333743.1566041013545
200ADS2370926.366057515070
250ADS309290.56.31020575200100
400ADS260510.36.31250575150120
800ADS50026A0.23.151800864285250
800ADS50026C0.23.151700864285250
1200ADS50027A0.13.6522001000300300
1200ADS50027C0.13.6519001000300300
1200ADS50027A0.13.6522001000300300
1200ADS50027C0.13.6519001000300300

Rated Voltage

  • 250VAC (SP&N) 50/60Hz
  • 440/250VAC (TP&N) 50/60Hz

Alternative Voltage

  • Also suitable for 208/120VAC and 480/277VAC
  • Alternative surge arrestors may be required.
  • TP&N filters are also suitable for three phase supplies without neutral. In such installations, the neutral terminal should be left unconnected.

Rated Current

  • 6A to 1200A (each individual line, see table)

Current Overload

  • 0 x maximum rated current for 1 sec.
  • 1.5 x max rated current for 10 minutes.

Discharge time

  • 30 seconds to below 30V (filter incorporates discharge resistors)
  • If sockets or plugs are used for connection, ensure that no pins or un-insulated parts are accessible by none qualified personnel upon removal

Temperature Rise

  • 25°C case rise on full load

Temperature Range

  • -45°C to +85°C Storage
  • -45°C to +50°C Working

MTBF

  • >0.8 million hours (calculated using Mil Hdbk 217D)

Surge Suppression (optional)

  • 275VAC at 215J 10kA 8/20μs
  • All filters can be supplied with an integral metal-oxide varistor, fitted between each input terminal and earth. Add a suffix “V” to end of part code.

All MPE installation filters are tested using the test methods defined within the following standards and meet or exceed the relevant performance and/or safety criteria defined within these standards:

  • Mil-F-15733
  • Mil-Std-220C
  • CISPR17:2011/BS EN 55017:2011
  • UL1283
  • LVD 2014/35/EU
  • NATO STANAG 1008 Ed.9 shipboard supplies
  • DEF-STAN 59-411/MIL-STD-461
  • RoHS (2011/65/EU) & LVD (2014/35/EU)
  • UKCA & CE
MPE Part CodeDescriptionNSN
DS2375216A Single Phase5915-99-968-7487
DS2333232A Single Phase5915-99-176-8426
DS2333463A Single Phase5915-99-152-3079
DS23336100A Single Phase5915-99-391-4527
DS23708200A Single Phase5915-99-156-5318
DS26050400A Single Phase5915-99-847-7146
DS236196A Three Phase5915-99-291-1718
DS2333110A Three Phase5915-99-377-6256
DS2333332A Three Phase5820-99-570-1166
DS2333563A Three Phase5915-99-371-3551
DS23337100A Three Phase5915-99-671-1575
DS23709200A Three Phase5915-99-959-4382
DS30929250A Three Phase5915-99-918-6144
DS26051400A Three Phase5915-99-845-4990