A range of multi-line filters suitable for filtering ac control lines and low current power lines on shielded rooms and general installations. All versions are available with transient suppression if required.

All MPE control line filters are tested using the test methods defined within the following standards and meet or exceed the relevant performance and/or safety criteria defined within these standards:

Mil-F-15733
Mil-Std-220C
CISPR17:2011/BS EN 55017:2011
UL1283
LVD 2014/35/EU

Rated Voltage250V a.c. 50/60Hz or 600V d.c.
Test Voltage2250V dc (prior to fitting any transient suppressors)
Rated Current1A to 10A
Insulation Resistance> 100MΩ (before fitting discharge resistors)
Discharge Resistors25560kΩ each line to case
Discharge time to below 34V< 10s
Maximum Temperature Rise on Full Load25ºC
Full Load Operating Temperature Range-40ºC to +50ºC
Current Rating (A)MPE Part NumberNumber Of LinesVolt Drop (mV)Heat  Dissipation (W)Major Dimensions (mm)Approx Weight (kg)
ABC
1DS2377822.72.735090452.5
2DS2579121.32.635090452.5
5DS2526021535090452.5
10DS2579420.7735090452.5
1DS2526342.72.7350180455
2DS2579241.32.6350180455
5DS25261415350180455
10DS2579540.77350180455
1DS2526482.72.73503604510
2DS2579381.32.63503604510
5DS252628153503604510
10DS2579680.773503604510

All multi-line filters can be supplied with integral transient suppression fitted between each input terminal and earth.

Varistor rating: 275V a.c. 45 Joules (10/1000μs)

To specify the transient suppressed version, suffix V is added to the filter part number (see ordering code).

The standard cable entry consists of an end conduit entry hole on the filter input (supply) side and a base conduit exit hole on the output (load) side.

Filters can be supplied with other cable entry positions if required upon request.