Please enter your email address below to download.
From screened rooms to industrial power equipment, uncontrolled radio interference presents a common hazard. This range of filters is designed specifically for use on single and three phase mains, and has all the advantages of using current compensating inductors.
All MPE installation filters are tested using the test methods defined within the following standards and meet or exceed the relevant performance and/or safety criteria defined within these standards:
Mil-F-15733
Mil-Std-220C
CISPR17:2011/BS EN 55017:2011
UL1283
LVD 2014/35/EU
Current Rating (A) | MPE Part Number | Performance Curve | Volt Drop (mV) | Heat Dissipation (W) | Major Dimensions (mm) | Case Size (see Installation Details Page Installation Details) | Approx Weight (kg) | ||
---|---|---|---|---|---|---|---|---|---|
A | B | C | |||||||
Single Phase (+N) | |||||||||
6 | DS23547 | 1 | 500 | 7 | 310 | 175 | 90 | a | 8 |
10 | DS23330 | 1 | 500 | 11 | 310 | 175 | 90 | a | 8 |
16 | DS23752 | 1 | 500 | 14 | 310 | 175 | 90 | a | 8 |
32 | DS23332 | 1 | 500 | 22 | 550 | 205 | 95 | e | 16 |
63 | DS23334 | 1 | 500 | 50 | 550 | 205 | 105 | f | 20 |
100 | DS23336 | 2 | 500 | 60 | 640 | 205 | 120 | i | 22 |
200 | DS23708 | 2 | 500 | 120 | 660 | 475 | 135 | u | 60 |
400 | DS26050 | 2 | 500 | 150 | 1250 | 475 | 150 | mm | 110 |
Three Phase (+N) | |||||||||
6 | DS23619 | 2 | 500 | 11 | 310 | 350 | 90 | b | 16 |
10 | DS23331 | 2 | 500 | 16 | 310 | 350 | 90 | b | 16 |
32 | DS23333 | 1 | 500 | 45 | 550 | 410 | 95 | g | 22 |
63 | DS23335 | 2 | 500 | 70 | 550 | 410 | 110 | h | 32 |
100 | DS23337 | 2 | 500 | 70 | 660 | 410 | 135 | j | 45 |
200 | DS23709 | 2 | 500 | 160 | 660 | 575 | 150 | v | 70 |
400 | DS26051 | 2 | 500 | 170 | 1250 | 575 | 150 | nn | 120 |
MPE Part Code | Description | NSN |
DS23547 | 6A Single Phase | 5915-99-310-0769 |
DS23330 | 10A Single Phase | 5820-99-310-8911 |
DS23752 | 16A Single Phase | 5915-99-968-7487 |
DS23332 | 32A Single Phase | 5915-99-176-8426 |
DS23334 | 63A Single Phase | 5915-99-152-3079 |
DS23336 | 100A Single Phase | 5915-99-391-4527 |
DS23708 | 200A Single Phase | 5915-99-156-5318 |
DS26050 | 400A Single Phase | 5915-99-847-7146 |
DS23619 | 6A Three Phase | 5915-99-291-1718 |
DS23331 | 10A Three Phase | 5915-99-377-6256 |
DS23333 | 32A Three Phase | 5820-99-570-1166 |
DS23335 | 63A Three Phase | 5915-99-371-3551 |
DS23337 | 100A Three Phase | 5915-99-671-1575 |
DS23709 | 200A Three Phase | 5915-99-959-4382 |
DS30929 | 250A Three Phase | 5915-99-918-6144 |
DS26051 | 400A Three Phase | 5915-99-845-4990 |
All types can be supplied with integral transient suppression fitted between each input terminal and earth.
Varistor rating: 275V a.c. 140 Joules (10/1000μs)
Other varistor ratings can also be supplied. To specify the transient suppressed version, suffix V is added to the filter part number (see ordering code).
The standard cable entry consists of an end conduit entry hole on the filter input (supply) side and a base conduit exit hole on the output (load) side.
Filters can be supplied with other cable entry positions if required upon request. Please refer to Installation Details page.
To facilitate installation of these filters, separate fixing kits are available to suit bulkhead panel thicknesses up to 20mm. Please refer to fixing kits product page.
DS XXXXX / X / X e.g. DS23330CV
Filter Part Number
Suffix C for standard cable entry
For other cable entries, see Installation Details page
Add suffix V for transient suppressed filter