MPE Low Leakage Installation Filter A

 

 

 

 

 

 

 

 

This range of single and three phase filters features a low leakage construction offering increased levels of safety. Applications include secure communications systems, computer installations, and portable screened enclosures. These filters are designed for use on mains supplies with a dedicated neutral.
All MPE installation filters are tested using the test methods defined within the following standards and meet or exceed the relevant performance and/or safety criteria defined within these standards:

Mil-F-15733
Mil-Std-220C
CISPR17:2011/BS EN 55017:2011
UL1283
EN60950/IEC60950

 

GENERAL SPECIFICATION

Rated Voltage – Single Phase Filters
250V a.c. 50/60Hz (also suitable for 2 line d.c. supplies up to 600V d.c. provided that load current returns through the filter)
Rated Voltage – Three Phase Filters
250/440V a.c. 50/60Hz
Rated Current
As tabulated
Insertion Loss
See graph and table
Performance curve 2 meets 100dB at 50kHz
Performance curve 3 meets 100dB at 100kHz
Maximum Temperature Rise on Full Load
25°C
Operating Temperature Range on Full Load
-45°C to +50°C
Maximum Full Load Heat Dissipation
As tabulated
Maximum Volt Drop per line at Full Load d.c. Current
500mV
Discharge time to below 34V
30s maximum
Maximum Continuous Earth Leakage Current
(per Neutral-Earth Volt at 50Hz)
As tabulated

RANGE AVAILABLE

Current Rating (A) MPE Part Number Performance Curve Leakage Current (mA) Heat Dissipation (W) Major Dimensions (mm) Case Size (see Installation Details Page Installation Details) Approx Weight (kg)
A B C
Single Phase (+N)
6 DS23550 2 15 7 425 175 90 c 12
10 DS23551 2 15 11 425 175 90 c 12
16 DS26231 2 15 14 425 175 90 c 12
32 DS23552 2 25 21 550 205 95 e 16
63 DS23553 3 25 50 725 205 105 l 23
100 DS23554 3 30 60 760 205 120 n 28
200 DS25915 3 50 120 820 475 150 x 80
400 DS25917 3 100 150 1250 475 150 mm 110
Three Phase (+N)
6 DS23620 3 30 10 425 350 90 d 18
10 DS23555 3 30 15 425 350 90 d 18
32 DS23556 3 45 42 590 410 95 w 24
63 DS23557 3 55 68 725 410 110 m 42
100 DS23558 3 95 70 780 410 135 p 55
200 DS25916 3 150 160 820 575 150 y 85
400 DS25918 3 150 170 1250 575 150 nn 120

TRANSIENT SUPPRESSION

All types can be supplied with integral transient suppression fitted between each input terminal and earth.

Varistor rating : 275V a.c. 140 Joules (10/1000µs)

Other varistor ratings can also be supplied. To specify the transient suppressed version, suffix V is added to the filter part number (see ordering code).

TYPICAL INSTALLATION DETAILS

The standard cable entry consists of an end conduit entry hole on the filter input (supply) side and a base conduit exit hole on the output (load) side.

Filters can be supplied with other cable entry positions if required upon request. Please refer to Installation Details page.

To facilitate installation of these filters, separate fixing kits are available to suit bulkhead panel thicknesses up to 20mm. Please refer to fixing kits product page.

ORDERING CODE

DS XXXXX / X / X e.g. DS23550CV

Filter Part Number

Suffix C for standard cable entry
For other cable entries, see Installation Details page

Add suffix V for transient suppressed filter