Extended Performance EMC Filter Range

Download

Please enter your email address below to download.

MPE Ext Performance Installation Filter A

 

 

 

 

 

 

 

 

This range of filters has been designed to meet the very highest insertion loss requirement of 100dB from 10kHz to 10GHz and features an extended low frequency performance to provide considerable filter attenuation at frequencies as low as 1kH

All MPE installation filters are tested using the test methods defined within the following standards and meet or exceed the relevant performance and/or safety criteria defined within these standards:

Mil-F-15733
Mil-Std-220C
CISPR17:2011/BS EN 55017:2011
UL1283
EN60950/IEC60950

GENERAL SPECIFICATIONS

Rated Voltage
Single Phase Filters
250V a.c. 50/60Hz (also suitable for 2 line d.c. supplies up to 600V d.c. provided that load current returns through the filter)
Three Phase Filters
250/440V a.c. 50/60Hz
Rated Current
As tabulated
Insertion Loss
100dB from 10kHz to 10GHz
Maximum Temperature Rise on Full Load
25°C
Operating Temperature Range on Full Load
-45°C to +50°C
Maximum Full Load Heat Dissipation
As tabulated
Maximum Volt Drop per line at Full Load d.c. Current
As tabulated
Discharge time to below 34V
30s maximum

RANGE AVAILABILITY

Current Rating (A) MPE Part Number Performance Curve Volt Drop (mV) Heat Dissipation (W) Major Dimensions (mm) Case Size (see Installation Details Page Installation Details) Approx Weight (kg)
A B C
Single Phase (+N)
6 DS25940 1 500 8 310 175 90 a 8
10 DS25941 1 500 11 310 175 90 a 8
16 DS25942 1 500 15 550 205 95 e 16
32 DS25943 1 500 25 550 205 95 e 18
63 DS25944 1 500 52 640 205 120 i 22
100 DS25945 1 500 60 660 475 135 u 60
200 DS26060 1 500 120 750 500 160 pp 75
400 DS26062 1 500 160 1050 525 185 qq 110
Three Phase (+N)
6 DS25946 1 500 12 310 350 90 b 16
10 DS25947 1 500 16 310 350 90 b 16
16 DS25948 1 500 25 550 410 95 g 22
32 DS25949 1 500 48 550 410 95 g 24
63 DS25950 1 500 70 660 410 135 j 45
100 DS25951 1 500 70 660 575 150 v 70
200 DS26061 1 500 120 750 700 170 rr 95
400 DS26063 1 500 240 1700 700 170 ss 200

TRANSIENT SUPPRESSION

All types can be supplied with integral transient suppression fitted between each input terminal and earth.

Varistor rating : 275V a.c. 140 Joules (10/1000µs)

Other varistor ratings can also be supplied. To specify the transient suppressed version, suffix V is added to the filter part number (see ordering code).

Typical Installation Details

The standard cable entry consists of an end conduit entry hole on the filter input (supply) side and a base conduit exit hole on the output (load) side.

Filters can be supplied with other cable entry positions if required upon request. Please refer to Installation Details page.

To facilitate installation of these filters, separate fixing kits are available to suit bulkhead panel thicknesses up to 20mm. Please refer to fixing kits product page.

ORDERING CODE

DS XXXXX / X / X e.g. DS25940CV

Filter Part Number

Suffix C for standard cable entry
For other cable entries, see Installation Details page

Add suffix V for transient suppressed filter